干(gan)式變(bian)壓器(qi)通過預埋(mai)在(zai)低壓繞組(zu)中的(de)(de)PTC非線性熱敏(min)測溫(wen)(wen)電阻,采集繞組(zu)或鐵心(xin)溫(wen)(wen)度信(xin)號(hao)。當(dang)干(gan)式變(bian)壓器(qi)繞組(zu)溫(wen)(wen)度繼續升(sheng)高,若達到155攝氏度時,系統輸出超溫(wen)(wen)報(bao)警信(xin)號(hao);若溫(wen)(wen)度繼續上(shang)升(sheng)達170攝氏度,干(gan)式變(bian)壓器(qi)不(bu)能繼續運行,須向二次保護回路輸送超溫(wen)(wen)跳閘信(xin)號(hao),應使變(bian)壓器(qi)迅速跳閘。法蘭(lan)表(biao)面(mian)高低不(bu)平,擰緊螺栓(shuan)松(song)脫,安裝加工工藝(yi)有誤,使螺栓(shuan)擰緊不(bu)太好(hao),先(xian)將松(song)脫的(de)(de)螺栓(shuan)擰緊,不(bu)然會導致(zhi)滲漏(lou)油。
干變風機(ji)外(wai)殼(ke),對法蘭執行密封性解決,并對于將會滲(shen)漏(lou)的螺栓(shuan)也開展解決,我們通過(guo)預埋在(zai)低壓(ya)繞(rao)組熱(re)處的熱(re)敏測溫(wen)電阻測取溫(wen)度信(xin)號,變壓(ya)器負荷(he)增大,運行溫(wen)度上升,當(dang)(dang)繞(rao)組溫(wen)度達110攝氏(shi)度時(shi),系(xi)(xi)統(tong)自(zi)動(dong)啟動(dong)風機(ji)冷卻(que)。當(dang)(dang)繞(rao)組溫(wen)度低至90攝氏(shi)度時(shi),系(xi)(xi)統(tong)自(zi)動(dong)停止風機(ji)。溫(wen)控器在(zai)正常測量(liang)工作狀(zhuang)態(tai)下(xia),按SET鍵(jian),進入參數設定狀(zhuang)態(tai)。組裝(zhuang)式外(wai)殼(ke)的框架是由(you)不銹鋼(gang)、鋁合金方(fang)管或矩管焊接或螺絲(si)緊固組成(cheng)。
框(kuang)架內嵌(qian)入(ru)1-2mm的不銹鋼(gang)板或(huo)鋁合金板封堵,不銹鋼(gang)板或(huo)鋁合金板根據(ju)框(kuang)架尺寸折邊(bian),嵌(qian)入(ru)框(kuang)架內,焊接或(huo)用螺絲或(huo)鉚釘(ding)固定。其(qi)上面開長(chang)條(tiao)孔(kong)(kong),但是窄邊(bian)方(fang)向的尺寸不得(de)大于12.5mm,滿足防(fang)護等級要(yao)(yao)求。如果長(chang)條(tiao)孔(kong)(kong)內加(jia)防(fang)塵網,如果用在室(shi)外,防(fang)護等級要(yao)(yao)高一些(xie),通風孔(kong)(kong)應設置(zhi)防(fang)雨百葉窗,且頂部不得(de)開通風散(san)熱(re)孔(kong)(kong)。鋼(gang)板外殼先要(yao)(yao)加(jia)工(gong)骨(gu)架、側(ce)板、門(men)板、連接件,然后焊接成左、右(you)側(ce)框(kuang),前、后門(men)框(kuang),進行酸洗磷化表面處(chu)理,再噴(pen)塑或(huo)噴(pen)漆,頂蓋上四個角(jiao)部均(jun)設計(ji)吊(diao)環。